DRT2-DA02 omron PLC

  • DRT2-DA02
  • DRT2-DA02

DRT2-DA02 omron PLC

Category:
Model DRT2-AD04 DRT2-AD04H DRT2-DA02
Communications power supply voltage 11 to 25 VDC (Supplied from the communications connector)
Current consumption 90 mA max. (24 VDC)
150 mA max. (11V DC)
70 mA max. (24 VDC)
110 mA max. (11 VDC)
120 mA max. (24 VDC)
220 mA max. (11 VDC)
Noise immunity Conforms to IEC61000-4-4, 2 kV (power line)
Vibration resistance 10 to 150 Hz, 0.7-mm double amplitude
Shock resistance 150 m/s2
Dielectric strength 500 VAC for 1 min between the communications circuit and analog circuit
(1 mA sensing current)
Ambient operating temperature -10°C to 55°C (with no icing or condensation)
Ambient operating humidity 25% to 85%
Ambient operating atmosphere No corrosive gases
Ambient storage temperature -20°C to 65°C
Mounting method DIN 35 mm-track mounting
Mounting strength 50 N
10 N (in the DIN Track direction)
Screw tightening torque M3 (power, I/O terminal): 0.5 Nm
Weight 170 g max. 160 g max. 150 g max.