Ambient temperature
Relative humidity
Anti-vibration When DIN rail is installed Frequency: 10 to 57 Hz
Frequency: 57 to 150 Hz
Direct installation Frequency: 10 to 57 Hz
Frequency: 57 to 150 Hz
Impact resistance
Noise immunity
Withstand voltage
Insulation resistance
ground
Use atmosphere
Use altitude
0 to 55 ° C. ··· Operating, -25 to 75 ° C. ····· Save
5 to 95% RH (noncondensing) · · · · in operation
One amplitude: 0.035 mm X, Y, Z 10 times in each direction (80 minutes in total) The
criteria are based on IEC 61131-2
Acceleration: 4.9 m / s 2 Ten times in each of X, Y, Z directions (total of 80 minutes each) The
criterion is based on IEC 61131-2
One amplitude: 0.075 mm X, Y, Z 10 times in each direction (80 minutes in total) The
criteria are based on IEC 61131-2
Acceleration: 9.8 m / s 2 X, Y, Z 10 times in each direction (80 minutes in total) The
criteria are based on IEC 61131-2
147 m / s 2 , working time 11 ms,
criterion for judgment three times in X, Y, Z directions by sine half-wave pulse is according to IEC 61131-2
Noise voltage with 1,000 Vp-p, noise width 1 μs, rising 1 ns, with noise simulator with period of 30 to 100 Hz
When performing the withstand voltage test, make the voltage between each terminal and the ground terminal of the basic unit as follows.
Between the power supply terminal (AC power supply) and the earth terminal: AC 1.5 kV 1 minute
DC 24 V service power supply and between the input terminal (24 VDC) and the earth terminal: 500 VAC for 1 min Between the
output terminal (relay) and the earth terminal: AC 1.5 kV 1 min
When conducting the insulation resistance test, perform the following voltage between each terminal and the ground terminal of the basic unit.
Between the power supply terminal (AC power supply) and the earth terminal: 500 MV
DC insulation resistance meter 5 MΩ or more DC 24 V service power supply and between the input terminal (24 VDC) and the earth terminal: 500 V DC 500 MΩ or more with the insulation resistance meter
Output terminal (relay) Between: 500 MV DC Insulation resistance meter 5 MΩ or more
Class D grounding (grounding resistance: 100 Ω or less) <Common grounding with high voltage system is not allowed>
Grounding must be dedicated ground or common ground.
There is no corrosive property, flammable gas, conductive dust (dust) is not serious
Can not be used in an environment pressurized to 2000 m or less under atmospheric pressure. It may break down.