HL-5200 omron limit switch

  • hl-5200
  • hl-5200

HL-5200 omron limit switch

SKU: 10 Category:
  • Shape / structure Vertical vertical type
    lifespan General form
    Actuator Seal, roller, plunger type
    Rated frequency 50/60 Hz
    Contact configuration 1a1b
    load General load
    Switching ability (AC) / no inductive load Rated load: 1.5 A (NC) 0.7 A (NO) Rated voltage: AC 250 V / resistance load: 5 A (NC) 5 A (NO) / lamp 
    load: 5 A (NC) 1A (NC) 0.5 A (NO)
    Switching capacity (AC) / inductive load Rated voltage: AC 250V / Inductive load: 3A (NC) 3A (NO) / Motor 
    load: 1.5 A (N / A) (NC) 0.8 A (NO)
    Switching ability (DC) / no inductive load Rated load: 3A (NC) 3A (NO) 
    Rated voltage: 24 VDC / resistance load: 5 A (NC) 5 A (NO) / lamp load: 3 A NC) 3A (NO) 
    Rated voltage: DC 125 V / resistance load: 0.4 A (NC) 0.2 A (NO) 
    Rated voltage: DC 250 V / resistance load: 0.4 A (NC) 0.2 A (NO)
    Switching capacity (DC) / inductive load Rated voltage: 
    24 VDC / Inductive load: 4 A (NC) 4 A (NO) / Motor load: 3 A (NC) 4 A (NO) / Inductive load: 4 A (NC) NC) 3A (NO)
    Allowable inrush current Normally closed (NC): 24 A 
    Always open (NO): 12 A
    Ambient temperature range At use: -5 to 65 ° C 
    (but do not freeze)
    Ambient humidity range When used: 35 to 95% RH 
    (with no condensation)
     
    Allowable operating speed 5 mm / s to 0.5 m / s
    Allowable operation frequency (mechanical) 120 times / min or less
    Allowable operation frequency (electrical) 30 times / minute or less
    Contact resistance (Initial value) 25 mΩ or less
    Insulation resistance 100 MΩ or more 
    (DC 500 V Mega)
    Withstand voltage Between terminals with the same polarity: AC 1000 V 50/60 Hz 1 min Between 
    charging metal part and earth: AC 1500 V 50/60 Hz 1 min Between 
    each terminal and non-charging metal part: AC 1500 V 50/60 Hz 1 min
    Durability (mechanical) 10 million times or more 
    (temperature and humidity condition: 5 to 35 ° C., 40 to 70% RH)
    Vibration proof (malfunction) 10 to 55 Hz Double amplitude 1.5 mm
    Impact resistance (durability) Up to 1000 m / s ** 2
    Impact resistance (malfunction) Maximum 300 m / s ** 2
    Protective structure IP65
     
    Power required for operation (OF) Standard value maximum 8.83 N
    The power of return (RF) Standard value Minimum 1.47 N
    Movement to action (PT) Standard value Maximum 1.5 mm
    Motion after movement (OT) Standard value minimum 4 mm
    Hysteresis movement (MD) Standard value Maximum 1 mm
    Operating position (OP) Standard value 40 ± 0.8 mm