Question 1: The F900GOT screen created with the GT Designer software will display “The display is invalid.” (No.0)
The main reason for this phenomenon is due to DU / WIN software editing screen number from 0 to 499, and GT Designer software editing screen number from 1 to 500, the screen switching element of the initial value of 0 (that is, No. 0 screen) And GT Designer software to edit the screen and no 0 screen. So the error will be given “the display is invalid. (No.0)”.
To do this, first enter the system screen of F900GOT, select “other mode” / “set mode” / “auxiliary setting”, and select “write” as “initial screen number”.

Question 2: GOT-F900 The keyboard window that pops up when the value is entered can not be closed after pressing the “ENTER” key
If the picture is made with FX-PCS-DU / WIN software, there is no such problem.
(I) If you are using the GT Designer software produced by the screen, the specific steps are as follows:
1. Right-click on the screen where the value is entered and select “Screen Property …” from the pop-up menu.
Or select “Common” / “Auxiliary Setting” / “Screen …” and click “Edit …”
2. In the “Screen Auxiliary Setting” dialog box appears in the “Cursor Movement” box, select “Clear cursor and key window” can be. The default setting for this item is “No Movement”.
Note: If you are using the GT Designer Chinese software, you can right click on the screen where the value is entered, select “Screen Properties …” in the pop-up menu or select “Public” / “Secondary Settings” / “Screen …” And click the “Edit …” button.

(Ii) If you are using the GT Designer2 software produced by the screen, the specific steps are as follows:
1. Right click on the numeric input screen and select “Screen Properties …” from the pop-up menu.
Or select “Screen” / “Properties …”
2. In the “Screen Property” dialog box, select “Auxiliary” tab, and in the “Cursor Movement” box, select “Clear cursor and key window” can be. The default setting for this item is “No Movement”.