Power-supply voltage | AC 100 to 240 V 50/60 Hz |
---|---|
Allowable voltage variation range | 85 to 110% of the rated power supply voltage |
power consumption | 12 VA / 2.5 W (AC 240 V) |
Time specification (number of ranges) | 1 |
Setting time range (each range) | 1 sec – 99 min 59 sec |
Range selection | Front thumb rotary switch |
input signal | Reset, gate |
Minimum external input signal width | 20 ms (reset, gate) |
Output mode | N (power on delay) |
Control output (contact output) | 1 c switching capacity (resistance load (cos φ = 1)): AC 250 V 3A / DC 24 V 3A minimum application load: DC 5 V 10 mA (P level, reference value) |
Return type | Power reset / External reset |
Power supply reset | Minimum power release time: 0.5 s |
Display mode | Subtraction (decrease from set value to 0) |
Display method | 7 segment LED |
Number of digits | 4 digits |
Character height | 10 mm (red) |
Ambient temperature range | At use: at -10 to 55 ° C Storage: -25 to 65 ° C |
Ambient humidity range | When used: 35 to 85% RH |
Total error | Variation in operation time, set error, influence of voltage, temperature influence, power supply rise time, internal circuit, output circuit operation time ± 0.01% ± 0.05 s or less (at power supply start) Ratio to set value Operation time variation , set error, the influence of the voltage, the influence of temperature, rise time of the power supply, the internal circuit, the operation time of the output circuit (for reset start) ± 0.005% ± 0.03s ratio set value |
Insulation resistance | 100 (with DC500 V mega) Between the conductive part terminal and the exposed uncharged metal part / between the operation power supply circuit and the control output circuit |
Withstand voltage | Between the conductive part terminal and the exposed non-charging metal part: 2000 Between the operation power supply circuit and the control output circuit: 2000 |
Impulse voltage | Between the power supply terminals: 6 kV between the conductive part terminal and the exposed non-charging metal part: 6 kV |
Noise immunity | Operation Supply terminal to terminal: ± 2 kV Square wave noise by noise simulator |
Electrostatic strength | 8 kV (malfunction) |
Vibration resistance (durability) | 10 to 55 Hz single amplitude 0.75 mm 3 directions 2 h each |
Vibration proof (malfunction) | 10 to 55 Hz One-half amplitude 0.5 mm 3 directions each 10 min |
Impact resistance (durability) | 300 m / s ** 2, 6 directions 3 times each |
Impact resistance (malfunction) | 100 m / s ** 2, 6 directions 3 times each |
Mechanical life | Over 10 million times |
Electrical life | 100 thousand times or more (AC 250 V 3A resistive load) |
Mounting method | Embedded mounting, surface mounting (common) |
External connection method | 8 pin socket |
Optional Accessories | Y92A – 48D: Soft cover Y92A – 48B: Hard cover Y92F – 30: Embedding adapter |
Mass (main body) | Approximately 110 g |